Choosing the right parallel groove clamp (PG clamp) starts with the conductors—not the clamp appearance. Confirm the main and tap conductor materials, sizes, construction and service conditions; then match them to a manufacturer-approved connector with suitable electrical performance, mechanical retention and installation instructions. For overhead distribution work, also verify the applicable utility specification and whether the joint is intended for an electrical tap, a jumper connection or another defined duty. A clamp that fits physically is not necessarily suitable electrically or mechanically.
A parallel groove clamp is a bolted electrical connector designed to hold two conductors in adjacent grooves and create an electrical connection between them. It is commonly used for overhead distribution taps and jumper connections where its design and ratings are approved for the conductors and application. The grooved body, clamping plates and fasteners work together to maintain contact pressure. Unlike an anchoring or dead-end fitting, a typical PG clamp is not intended to carry the full tensile load of a conductor span unless a specific design is explicitly rated for that purpose.
PG clamps are sometimes called parallel groove connectors or bolted line connectors. These terms describe a family of products rather than one universal design. Conductor compatibility, fastener arrangement and installation requirements can differ substantially between models.


The connector positions two conductors side by side. When the specified fasteners are tightened according to the manufacturer’s instructions, the clamp applies pressure across the contact interfaces. The resulting joint must provide adequate electrical contact and resist loosening under its intended service conditions. Surface condition, conductor preparation, contact geometry and correct tightening all affect performance.
A PG clamp does not automatically pierce insulation. Many designs are intended for bare conductors or require conductor preparation according to their instructions. Do not confuse a conventional PG clamp with an insulation piercing connector (IPC), which uses a different contact mechanism. Never remove insulation or install a connector on an energized line without the approved procedure and appropriately qualified personnel.
Identify whether each conductor is aluminum, copper, aluminum alloy or another specified construction. A clamp described as “aluminum” is not automatically approved for every aluminum conductor, and a standard single-metal connector should not be assumed suitable for a copper-to-aluminum joint. Where dissimilar metals are involved, obtain explicit manufacturer approval for that conductor pairing and the intended environment. A suitable bimetallic connector or other approved transition solution may be required.
Record the size of both conductors independently, normally in mm² or AWG/kcmil as required by the project. Check the actual approved range for each groove; some connectors have different limits for the main and tap sides. Also confirm conductor outside diameter and construction, because stranded and compacted conductors of the same nominal area can have different dimensions. Do not select by a model number alone.
Check whether the connector is approved for the conductor type and strand construction. Consider surface oxidation, contamination, corrosion and any required joint compound or preparation method. Use only the preparation procedure approved by the connector manufacturer and utility; aggressive cleaning or unapproved compounds can damage conductors or alter joint performance.
Review the body material, fastener material, coating and contact surfaces. These choices affect compatibility and long-term exposure behavior. Bolt count can influence the physical design and pressure distribution, but a three-bolt clamp is not automatically superior to a two-bolt clamp. Evaluate the tested connector assembly and the applicable specification rather than using bolt count as a shortcut for electrical capacity.
Determine whether the connection is a distribution tap, jumper, grounding connection or another application. Verify current-carrying suitability and any temperature-rise, short-circuit or mechanical requirements specified by the utility or project. A PG clamp should not be treated as a strain clamp unless the manufacturer explicitly documents the relevant tensile rating. For structural support or termination, select the appropriate anchoring hardware.
Overhead connections may face rain, humidity, pollution, salt spray and temperature cycling. Ask how the specified clamp design addresses the actual exposure conditions, including corrosion compatibility and any sealing or protective accessories. Avoid broad assumptions such as “all outdoor PG clamps are waterproof”; performance depends on the specific connector and installation system.
Use the exact installation sequence and tightening torque specified for the selected model. The correct value cannot be inferred from the clamp size or number of bolts. Where a torque-controlled method is required, use a suitable calibrated tool. Follow utility procedures for isolation, access, conductor support and inspection. Never apply a generic torque figure taken from an unrelated product.
|
Type |
Typical selection consideration |
Important limitation |
|
Aluminum-body PG clamp |
Often evaluated for approved aluminum-conductor connections |
Confirm exact conductor alloy, size and application |
|
Copper-body PG clamp |
May be specified for compatible copper-conductor connections |
Do not assume suitability for aluminum |
|
Bimetallic or transition design |
Considered where approved dissimilar-metal joining is required |
Approval must cover the exact conductor pairing |
|
Two-bolt design |
One available bolted configuration |
Bolt count alone does not establish rating |
|
Three-bolt design |
Another available bolted configuration |
Check dimensions, torque and tested duty |
The categories above are general design families, not a specification sheet for any particular CNNILED model. A purchase decision must be based on the current drawing, data sheet and application approval for the selected product.
Suppose an overhead distribution project requires a tap between an aluminum main conductor and a smaller aluminum branch conductor. First record both nominal cross-sectional areas and actual conductor constructions. Next identify the connection duty and utility standard. Then compare only PG clamp data sheets that explicitly cover both conductor sizes and materials. Finally verify installation instructions, environmental requirements and any test documentation. If the project instead connects copper to aluminum, restart the material-compatibility check rather than reusing the aluminum-to-aluminum selection.
This example deliberately does not assign a model number or torque: those decisions require verified product data and project requirements.



CNNILED supplies overhead electrical line fittings and publishes a Parallel Groove Clamp application page. Buyers should use the current CNNILED product drawing and technical data sheet to confirm the available PG clamp models and the approved conductor combinations before requesting a quotation. The company’s public application page is an entry point, but its general marketing description is not a substitute for model-specific engineering data.
Explore the CNNILED Parallel Groove Clamp information page: https://www.cnniled.com/application/parallel-groove-clamp
|
Information to request |
Why it matters |
|
Exact model and product drawing |
Confirms identity, dimensions and hardware configuration |
|
Main and tap conductor ranges |
Confirms both sides of the joint are covered |
|
Approved conductor materials and construction |
Prevents incompatible conductor combinations |
|
Installation method and torque |
Supports consistent field installation |
|
Applicable test reports or standards |
Allows project-specific technical review |
|
Packaging, MOQ and lead time |
Supports distributor and contractor procurement |
For a technical comparison, request a side-by-side manufacturer data sheet rather than assuming that similar-looking clamps are interchangeable. Product-specific claims should be checked against the latest CNNILED documentation.
A parallel groove clamp joins two compatible conductors in a bolted, side-by-side electrical connection. Common applications include overhead distribution taps and jumpers, subject to the selected connector’s approved duty. It is not automatically a load-bearing strain or dead-end fitting.
Check both main and branch conductor ranges on the exact model data sheet. Verify conductor material, nominal cross-sectional area, outside diameter and construction. A connector that accepts one conductor size may not accept the other, and the two grooves may have different ranges.
Only when the specific connector is approved for that dissimilar-metal combination and its intended environment. Do not assume that an ordinary aluminum or copper PG clamp is suitable. Request written confirmation of the material pairing and any required installation accessories.
Not necessarily. Bolt count describes one design feature, not the complete electrical or mechanical rating. Compare the approved conductor ranges, contact design, testing, installation torque and project specification for each model before selecting.
Installation must follow the exact manufacturer instructions and the utility’s electrical safety procedures. Qualified personnel should confirm conductor preparation, clamp orientation, tightening sequence, torque and inspection requirements. There is no safe universal torque or preparation method for every PG clamp.
Provide the main and tap conductor materials and sizes, conductor construction, intended connection duty, environmental conditions, required standard or test documentation, estimated order quantity and destination. A drawing or photograph of the existing approved connector can also help identify the correct product.
The right parallel groove clamp is the one whose documented conductor compatibility, electrical duty, mechanical role, environmental suitability and installation requirements match the project. Start with both conductors and the utility specification, then evaluate model-specific technical data. For distributors, EPC contractors and utility buyers, this approach reduces ambiguity during sourcing and technical approval.
CNNILED welcomes inquiries about parallel groove clamps and other overhead electrical line fittings. Share your conductor specifications, drawings and estimated quantities so the team can review suitable options and provide product information or a quotation. Visit https://www.cnniled.com/ to contact CNNILED.
SEO Title: Parallel Groove Clamp Selection Guide for Overhead Lines
Meta Description: Learn how to choose a parallel groove clamp for overhead lines by conductor material, size, application, environment and installation requirements.
SEO Keywords: parallel groove clamp, PG clamp, overhead line connector, parallel groove connector, aluminum PG clamp, copper PG clamp, bolted connector, power distribution fittings, PG clamp selection guide
URL Slug: how-to-choose-parallel-groove-clamp
Category: Selection Guides
Excerpt: Selecting a parallel groove clamp requires more than matching conductor size. This guide explains conductor compatibility, material choices, electrical and mechanical duties, environmental exposure, installation requirements and the information buyers should include in a quotation request. It also highlights common selection mistakes and questions to verify with the manufacturer.